METTA Borehole pump panels – Main materials ABB

Designed and built by IDATOR, the AB1 series pump control panels combine manufacturing precision with the versatility of the METTA line.
Available in 230V or 400V, with power ratings up to 5.5kW, they offer solutions for both residential and professional borehole systems.

Category: Brand:

Designed and built by IDATOR, the AB1 series pump control panels combine manufacturing precision with the versatility of the METTA line.
Available in 230V or 400V, with power ratings up to 5.5kW, they offer solutions for both residential and professional borehole systems.
Every panel is housed in a watertight IP54 enclosure, plastic or metal depending on the application.
Integrated protections include overload, short circuit, phase failure, and voltage monitoring with adjustable thresholds.
Start-up types include direct or star-delta, with thermal or magnetic protection, depending on model.
Standard features include level monitoring with electrodesmanual/auto selector, and status indicator lights.
All units are accompanied by a wiring diagram and offer compatibility with floats, timers, and push-buttons.
Optional features include free voltage contactsdigital instrumentsLED lighting, and cosφ-based dry-run protection.
Built entirely in-house, every panel reflects IDATOR’s strict quality control and electrical design expertise.
METTA panels deliver a modular, ready-to-install solution tailored to field conditions — fast, durable, and smart.

START-UP PANEL FOR BOREHOLE PUMP 230V UP TO 2,2KW AB1D1___

  • Plastic watertight cabinet of protection class IP54
  • General bipolar load switch
  • Thermomagnetic switch depending on the current drawn by the pump to protect against overload, overcurrent, short circuit
  • Starter for direct starting of the pump
  • Capacitor connection, if required (not included)
  • Level monitor for detecting lack of water with electrodes
  • I-0-II selector switch for manual or automatic operation
  • Contact for operation with float, push button or timer in automatic mode
  • Indicator lights for operation, fault, water shortage
  • Connection terminal block accompanied by wiring diagram

START-UP PANEL FOR BOREHOLE PUMP 400V UP TO 5,5KW AB1D3___

  • Plastic watertight cabinet of protection class IP54
  • General load switch
  • Voltage, asymmetry, sequence and out-of-phase monitor with adjustable cut-off and reset times
  • Thermomagnetic switch according to the current drawn by the pump for protection against overload, overcurrent, short circuit
  • Starter for direct starting of the pump
  • Level monitor for detecting lack of water with electrodes
  • I-0-II selector switch for manual or automatic operation
  • Contact for operation with float, push button or timer in automatic mode
  • Indicator lights for operation, fault, voltage fault, water shortage
  • Connection terminal block accompanied by wiring diagram

START-UP PANEL FOR BOREHOLE PUMP 400V UP TO 5,5KW AB1Y3___

  • Metal watertight cabinet of protection class IP54
  • General load switch
  • Voltage, asymmetry, sequence and out-of-phase monitor with adjustable cut-off and reset times
  • Automatic ‘K’ curve fuses in combination with thermal relay, suitable for motor protection against overcurrent, short circuit and overload, or alternatively thermomagnetic circuit breaker
  • H/D starter sized according to the pump capacity
  • Level monitor for detecting lack of water with electrodes
  • I-0-II selector switch for manual or automatic operation
  • Contact for operation with float, push button or timer in automatic mode
  • Indicator lights for operation, fault, voltage fault, water shortage
  • Connection terminal block accompanied by a wiring diagram
CODE ADDITIONS
F Free voltage contacts for indication of operation, fault and lack of water (for AB1D1__ PANELS)
Free voltage contacts for operation, fault and water shortage indication (for PANEL AB1D1__ and AB1Y3__)
M 3-display instrument with voltage transformers
L Digital borehole level indicator (weight gauge not included)
P Protection against dry operation via drilling power factor (cosf) without Autoreset
Χ Reinforced universal socket
Ε LED interior lighting
  • Control and automation panels for starting a wide range of borehole pumps.
  • Protection against dry running of the pump in case of water shortage by means of level electrodes or digital level indicator.
  • Start-up command via pushbutton, timer or adjustable differential level float switch with counterbalance.
SINGLE BOREHOLE PUMP START-UP PANELS
Type Voltage Hp KW Start-up Range A Box material Protection Dimensions
H x W x D (mm)
ΑB1D1007 230V 1 0,75 DOL 4-6,3 ABS
IP54
400x300x170
ΑB1D1011 1,5 1,1 6,3-10 400x300x170
ΑB1D1015 2 1,5 10-16 400x300x170
ΑB1D1022 3 2,2 10-16 400x300x170
ΑB1D3007 400V 1 0,75 DOL 1,6-2,5  

ABS

 

 

IP54

 

400x300x170
ΑB1D3011 1,5 1,1 2,5-4 400x300x170
ΑB1D3015 2 1,5 4-6,3 400x300x170
ΑB1D3022 3 2,2 4-6,3 400x300x170
ΑB1D3030 4 3 6,3-10 400x300x170
ΑB1D3040 5,5 4 6,3-10 400x300x170
ΑB1D3055 7,5 5,5 10-16 400x300x170
Α1D3075 10 7,5 16-20 400x300x170
ΑB1Υ3055 400V 7,5 5,5  

Υ/Δ

 

10-16*  

METAL

 

 

IP54

 

500x400x200
ΑB1Υ3075 10 7,5 16-20* 500x400x200
ΑB1Υ3110 15 11 23-26 600x400x200
ΑB1Υ3150 20 15 30-34 600x400x200
ΑB1Υ3185 25 18,5 35-41 700x500x200
ΑB1Υ3220 30 22 42-50 700x500x200
ΑB1Υ3300 40 30 52-68 800x600x200
ΑB1Υ3370 50 37 63-80 800x600x200

In the AB1Y3__ series a fuse with a thermal switch is used except for the asterisks where a thermomagnetic fuse is used.

  • Construction with ABB main materials
Scroll to Top