METTA electrical panels for surface pumps are designed for proper operation and control of the pumps, ensuring at the same time their protection by means of level electrodes or float switch.
METTA twin surface pump starting panels – Main materials CHINT
METTA electrical panels for surface pumps are designed for proper operation and control of the pumps, ensuring at the same time their protection by means of level electrodes or float switch.
Category: Control Panels
Brand: METTA
TWIN SURFACE PUMP STARTING TABLE 230V UP TO 2,2KW CS2D1___
- Plastic watertight enclosure of protection class IP54
- General bipolar load switch
- Automatic fuse depending on the current drawn by the pump to protect against overcurrent, short circuit
- Power starter, one for each pump for direct starting
- Thermal relay to protect the pump against overload
- Possibility of connecting a float switch or level electrodes to protect against water shortage
- Epilogical switch I-0-II, one for each pump to select manual or automatic operation
- Automatic operation with alternation of the starting order of the pumps in each new operating cycle and parallel operation of both pumps in case of activation of the parallel operation command
- Contacts for operation with floats, pressure switches or timers in automatic operation
- Indicator lights for operation, fault
- Connection terminal block accompanied by wiring diagram
TABLE FOR STARTING TWIN SURFACE PUMPS WITH U/D PRIMING CS2Y3___
- IP54 metal sealed enclosure
- General load break switch
- Asymmetry, sequence and out-of-phase monitor
- Automatic “D” curve fuses combined with thermal relay, suitable for overcurrent protection of motors, short-circuit and overload, or alternatively thermomagnetic switch
- HRC starter, one for each pump, sized according to the pump capacity
- Possibility of connecting a float switch or level electrodes for protection against water shortage
- I-0-II epilogical switch, one for each pump to select manual or automatic operation
- Automatic operation with alternation of the starting order of the pumps in each new operating cycle and parallel operation of both pumps in case of activation of the parallel operation command
- Contacts for operation with floats, piezostats or timers in automatic operation
- Indicator lights for operation, fault, voltage error
- Connection terminal block accompanied by wiring diagram
START-UP TABLE FOR TWIN SURFACE PUMPS 400V UP TO 5,5KW CS2D3___
- Plastic watertight enclosure of protection class IP54
- General load switch
- Asymmetry, sequence and phase failure monitor
- Thermomagnetic switch according to the current drawn by the pump to protect against overload, overcurrent, short circuit
- Power starter, one for each pump for direct starting
- Possibility of connecting a float switch or level electrodes to protect against water shortage
- Epilogical switch I-0-II, one for each pump to select manual or automatic operation
- Automatic operation with alternation of the starting order of the pumps in each new operating cycle, and parallel operation of both pumps in case of activation of the parallel operation command
- Contacts for operation with floats, piezostats or timers in automatic operation
- Indicator lights for operation, fault, voltage error
- Connection terminal block accompanied by wiring diagram
| CODE | ADDITIONS |
| F |
Free voltage contacts for operation and fault indication (for CS2D1__ panels) |
| Free voltage contacts for operation, fault and voltage fault indication (for CS2D3__and CS2Y3__ panels) | |
| M | 3-display instrument with voltage transformers |
| P | Protection against dry operation by measuring power factor (cosφ) without Autoreset |
| Χ | Reinforced universal socket |
| Ε | LED interior lighting |
- Control and automation panels for starting a wide range of surface pumps.
- Protection against dry running of pumps in the event of drainage of the pumping tank, by means of a float switch or level electrodes.
- Starting of the pumps by means of a pressure switch, timer or adjustable differential level float switch with counterweight.
| START-UP TABLES FOR 1 DRILLING PUMP | ||||||||
| Type | Voltage | Hp | KW | Start-up | Range A | Box material | Protection | Dimensions H x W x D (mm) |
|
CS2D1007
|
230V | 1 | 0,75 | DOL | 4-6 | ABS |
IP54 |
500x400x180 |
| CS2D1011 | 1,5 | 1,1 | 5,5-8 | 500x400x180 | ||||
| CS2D1015 | 2 | 1,5 | 7-10 | 500x400x180 | ||||
| CS2D1022 | 3 | 2,2 | 9-13 | 500x400x180 | ||||
| CS2D3007 | 400V | 1 | 0,75 | DOL | 1,6-2,5 | ABS |
IP54 |
500x400x180 |
| CS2D3011 | 1,5 | 1,1 | 1,6-2,5 | 500x400x180 | ||||
| CS2D3015 | 2 | 1,5 | 2,5-4 | 500x400x180 | ||||
| CS2D3022 | 3 | 2,2 | 4-6,3 | 500x400x180 | ||||
| CS2D3030 | 4 | 3 | 6-10 | 500x400x180 | ||||
| CS2D3040 | 5,5 | 4 | 6-10 | 500x400x180 | ||||
| CS2Y3055 | 400V | 7,5 | 5,5 | Υ/Δ |
9-14* | METAL |
IP54 |
600x500x200 |
| CS2Y3075 | 10 | 7,5 | 13-18* | 600x500x200 | ||||
| CS2Y3110 | 15 | 11 | 20-25* | 600x500x200 | ||||
| CS2Y3150 | 20 | 15 | 21-29 | 600x500x200 | ||||
| CS2Y3185 | 25 | 18,5 | 30-36 | 700x500x200 | ||||
| CS2Y3220 | 30 | 22 | 30-43 | 700x500x200 | ||||
| CS2Y3300 | 40 | 30 | 40-55 | 800x600x200 | ||||
| CS2Y3370 | 50 | 37 | 52-69 | 800x600x200 | ||||
In the CS2Y3___ series a fuse with a thermal switch is used except for the asterisks where a thermomagnetic fuse is used.
- Construction with main materials CHINT