METTA twin surface pump starting panels – Main materials CHINT

METTA electrical panels for surface pumps are designed for proper operation and control of the pumps, ensuring at the same time their protection by means of level electrodes or float switch.

Category: Brand:

METTA electrical panels for surface pumps are designed for proper operation and control of the pumps, ensuring at the same time their protection by means of level electrodes or float switch.

TWIN SURFACE PUMP STARTING TABLE 230V UP TO 2,2KW CS2D1___

  • Plastic watertight enclosure of protection class IP54
  • General bipolar load switch
  • Automatic fuse depending on the current drawn by the pump to protect against overcurrent, short circuit
  • Power starter, one for each pump for direct starting
  • Thermal relay to protect the pump against overload
  • Possibility of connecting a float switch or level electrodes to protect against water shortage
  • Epilogical switch I-0-II, one for each pump to select manual or automatic operation
  • Automatic operation with alternation of the starting order of the pumps in each new operating cycle and parallel operation of both pumps in case of activation of the parallel operation command
  • Contacts for operation with floats, pressure switches or timers in automatic operation
  • Indicator lights for operation, fault
  • Connection terminal block accompanied by wiring diagram

TABLE FOR STARTING TWIN SURFACE PUMPS WITH U/D PRIMING CS2Y3___

  • IP54 metal sealed enclosure
  • General load break switch
  • Asymmetry, sequence and out-of-phase monitor
  • Automatic “D” curve fuses combined with thermal relay, suitable for overcurrent protection of motors, short-circuit and overload, or alternatively thermomagnetic switch
  • HRC starter, one for each pump, sized according to the pump capacity
  • Possibility of connecting a float switch or level electrodes for protection against water shortage
  • I-0-II epilogical switch, one for each pump to select manual or automatic operation
  • Automatic operation with alternation of the starting order of the pumps in each new operating cycle and parallel operation of both pumps in case of activation of the parallel operation command
  • Contacts for operation with floats, piezostats or timers in automatic operation
  • Indicator lights for operation, fault, voltage error
  • Connection terminal block accompanied by wiring diagram

START-UP TABLE FOR TWIN SURFACE PUMPS 400V UP TO 5,5KW CS2D3___

  • Plastic watertight enclosure of protection class IP54
  • General load switch
  • Asymmetry, sequence and phase failure monitor
  • Thermomagnetic switch according to the current drawn by the pump to protect against overload, overcurrent, short circuit
  • Power starter, one for each pump for direct starting
  • Possibility of connecting a float switch or level electrodes to protect against water shortage
  • Epilogical switch I-0-II, one for each pump to select manual or automatic operation
  • Automatic operation with alternation of the starting order of the pumps in each new operating cycle, and parallel operation of both pumps in case of activation of the parallel operation command
  • Contacts for operation with floats, piezostats or timers in automatic operation
  • Indicator lights for operation, fault, voltage error
  • Connection terminal block accompanied by wiring diagram

 

CODE ADDITIONS
F

Free voltage contacts for operation and fault indication (for CS2D1__ panels)
Free voltage contacts for operation, fault and voltage fault indication (for CS2D3__and CS2Y3__ panels)
M 3-display instrument with voltage transformers
P Protection against dry operation by measuring power factor (cosφ) without Autoreset
Χ Reinforced universal socket
Ε LED interior lighting
  • Control and automation panels for starting a wide range of surface pumps.
  • Protection against dry running of pumps in the event of drainage of the pumping tank, by means of a float switch or level electrodes.
  • Starting of the pumps by means of a pressure switch, timer or adjustable differential level float switch with counterweight.
START-UP TABLES FOR 1 DRILLING PUMP
Type Voltage Hp KW Start-up Range A Box material Protection Dimensions
H x W x D (mm)
CS2D1007
230V 1 0,75 DOL 4-6 ABS

IP54

500x400x180
CS2D1011 1,5 1,1 5,5-8 500x400x180
CS2D1015 2 1,5 7-10 500x400x180
CS2D1022 3 2,2 9-13 500x400x180
CS2D3007 400V 1 0,75 DOL 1,6-2,5



ABS








IP54




500x400x180
CS2D3011 1,5 1,1 1,6-2,5 500x400x180
CS2D3015 2 1,5 2,5-4 500x400x180
CS2D3022 3 2,2 4-6,3 500x400x180
CS2D3030 4 3 6-10 500x400x180
CS2D3040 5,5 4 6-10 500x400x180
CS2Y3055 400V 7,5 5,5


Υ/Δ




9-14*



METAL








IP54




600x500x200
CS2Y3075 10 7,5 13-18* 600x500x200
CS2Y3110 15 11 20-25* 600x500x200
CS2Y3150 20 15 21-29 600x500x200
CS2Y3185 25 18,5 30-36 700x500x200
CS2Y3220 30 22 30-43 700x500x200
CS2Y3300 40 30 40-55 800x600x200
CS2Y3370 50 37 52-69 800x600x200

In the CS2Y3___ series a fuse with a thermal switch is used except for the asterisks where a thermomagnetic fuse is used.

  • Construction with main materials CHINT
Scroll to Top